Page 1
TP48200A-HX09A2, TBC300A-TCA2 Outdoor Power System User Manual Issue Date 2019-02-26 HUAWEI TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
2.2 Power Distribution Unit .............................. 10 2.3 Rectifier ..................................13 2.4 SMU02B ..................................15 2.5 UIM02C ..................................19 2.6 Temperature Control Unit (for the TP48200A-HX09A2) ................... 22 2.6.1 Heat Exchange ................................. 22 2.7 Temperature Control Unit (for the TBC300A-TCA2) ....................23 2.7.1 TEC ..................................23 2.8 Sensors and Lamp ...............................
1 Overview Overview 1.1 Overview The TP48200A-HX09A2 is a south-type heat exchange power cabinet that supplies power to -48 V DC outdoor communications equipment. The TBC300A-TCA2 is a thermoelectric cooler (TEC) battery cabinet that backs up power for communications equipment.
Network application over a fast Ethernet (FE) port and an RS485/RS232 port. Communication with Huawei NetEco or third-party network management systems (NMSs) over protocols such as the Simple Network Management Protocol (SNMP) and Hypertext Transfer Protocol Secure (HTTPS) to enable remote management and unattended working.
The SMU monitors and regulates the temperature control unit based on the temperature measured by the temperature sensor to ensure the normal operating temperature for the cabinet. Figure 1-5 Conceptual diagram 1.5 Configurations Table 1-1 describes the system configurations for the TP48200A-HX09A2, and TBC300A-TCA2. Table 1-1 Configurations Item TP48200A-HX09A2 TBC300A-TCA2...
Page 16
TP48200A-HX09A2, TBC300A-TCA2 Outdoor Power System User Manual 2 Components Figure 2-1 Interior of the TP48200A-HX09A2 (1) AC output circuit breaker (2) Maintenance socket (3) Load circuit breaker (4) AC SPD (surge protective device) (5) AC input circuit breaker (6) SMU...
(7) Ground bar 2.2 Power Distribution Unit AC PDU Figure 2-3 Figure 2-4 show the AC PDU for the TP48200A-HX09A2. Figure 2-3 AC input unit (1) AC input circuit (2) AC input terminal (3) AC surge protective Issue 02 (2019-02-26)
Page 18
Figure 2-4 AC output unit (Multi-purpose socket and RCD) (1) All-purpose socket (2) RCD (3) AC load circuit breaker and neutral wire terminal Table 2-1 describes the AC PDU configurations for the TP48200A-HX09A2. Table 2-1 AC PDU configurations Power Grid AC Input AC Surge...
SMOKE SMOKE BTEMP BTEMP 2.6 Temperature Control Unit (for the TP48200A-HX09A2) 2.6.1 Heat Exchange The equipment compartment of the power cabinet adopts heat exchanging to cool the equipment compartment, in which heat is exchanged through internal circulation and external circulation.
When operating Huawei equipment, in addition to following the general precautions in this document, follow the specific safety instructions given by Huawei. Only trained and qualified personnel are allowed to install, operate, and maintain Huawei equipment. This product should be used in the environment that meets design specifications.
Page 40
Only qualified professional personnel are allowed to install, configure, operate, and disassemble the device. Only the personnel authenticated or authorized by Huawei are allowed to replace or change the device of the parts of the device (including the software). Issue 02 (2019-02-26)
4-2. Figure 4-2 Installing a new rectifier Step 7 Take off protective gloves. ----End Follow-up Procedure Pack the removed component, and return it to Huawei local warehouse. 4.4.2 Replacing an SMU Prerequisites The cabinet door key is available. ...
Step 5 Reset the parameters on the SMU. Figure 4-4 Installing an SMU ----End Follow-up Procedure Pack the removed component and send it to the local Huawei warehouse. 4.4.3 Replacing the PCB of UIM02C Prerequisites An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and required tools are available.
Step 12 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist strap and ESD gloves. ----End Follow-up Procedure Pack the removed component and return it to the local Huawei warehouse. 4.4.4 Replacing an AC SPD Prerequisites ...
TP48200A-HX09A2: ≤ 75 kg (without rectifiers) Cabinet weight TBC300A-TCA2: ≤ 56 kg (without batteries) Protection level IP55 TP48200A-HX09A2: installed on a floor, installed against a Installation mode wall, combined with a battery cabinet, or stacked on a battery cabinet Issue 02 (2019-02-26)
Need help?
Do you have a question about the TP48200A-HX09A2 and is the answer not in the manual?
Questions and answers