Install the Telescopic Rail Runner on the Rack

Rack rail runners require a minimum of 48 cm and a maximum of 80 cm within the rack for installation.
1 Determine the location of the RealPresence Collaboration Sever (RMX) 4000 on the rack:
 Allow for a 1U gap above and below the system for ventilation.
 Use the rack spacer (3) to predetermine its position on the rack post, making sure that the square
studs of the spacer fit into the rack post square/rounded mounting holes. Mark the spacer location
on the rack post. Repeat this process for the 3 remaining vertical posts ensuring that the system
can be horizontally seated.
.