Manual Operation; Manual Operation For Outputs K1, K2 Or K3 - JUMO 202550 Operating Instructions Manual

Up indicator/controller for analytical measurement
Table of Contents

Advertisement

28 Manual operation

Description
Initial
condition

28.1 Manual operation for outputs K1, K2 or K3

Activate
86
In manual operation, outputs K1, K2 and K3 can be operated by hand,
independently of the controller.
Manual operation is only possible if it has been configured first.
Chapter 26.4 "Controller options - C211", page 76.
The output level limiting is effective during manual operation
(except for limit controllers).
The instrument is in the measurement mode.
In manual operation, outputs K1, K2 and K3 can be operated by hand.
+
1 s
EXIT
EXIT
Press keys
+
EXIT
1". The upper LED display switches between the momentary value and the
text "HAnd", the lower display shows the present temperature.
Activate or deactivate a particular output, see table
Key
PGM
Return to measurement mode with
1
Output level will be 0 / 100% for a proportional controller.
2
Only while the key is pressed. Only when the third relay is fitted ("Output
310",
Chapter 4.1 "Type designation", page 9).
for less than 1 second – this starts "Manual operation
EXIT
Output
1
K1
1
K2
2
K3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents