26 Configuration level (not instrument-specific)
26.2 SoL - SoH - SPL - SPH - OFFS - SiL - SiH
SoL
120%
100%
SoH
SPL
SPH
OFFS
Standard signal scaling of the analog process value output.
Start value of the range for standard signals of the process value output.
SoL1 -> Output 3
SoL2 -> Output 5
Value range:
depending on configuration -1.00 to 14.00 pH
Factory setting
Example 1:
4 — 20 mA should correspond to 2.00 — 9.00 pH
-> SoL = 2.00 / SoH = 9.00
Example 2:
0— 20 mA should correspond to -10 to +40°C
-> SoL = -10.0 / SoH = 40.0
Example 3:
0 — 100% of the controller output should correspond to 0 — 8 V of the output
signal (but the standard output signal of the controller is 0 — 10 V)
-> SoL = 0 / SoH = 120
0
Standard signal scaling of the analog process value output.
End value of the range for standard signals of the process value output.
SoH1 -> Output K3
SoH2 -> Output K5
For value ranges and factory settings, see "SoL" above.
Setpoint limiting for controller setpoints.
This parameter is used to define the lower limit setting for the controller
setpoints SPr1/2/3/4.
Setpoint limiting for controller setpoints.
This parameter is used to define the upper limit setting for the controller
setpoints SPr1/2/3/4.
Process value correction for temperature
The process value correction can be used to correct the measured value of the
50.0 to +250°C
-1.00 pH
8V
10V
81