12.14.4 How the Panel Works in Mode 14
•
Activation of any one among Z-1, Z-2, Z-3 or Z4 changes Hazard Area 1 state into
Alarm. Release Timer-1 is started. NAC-1 turns on steady. NAC-2 turns on Temporal if
the release timer is non-zero. Upon the expiration of Release Timer-1, both NAC-1 and
NAC-2 turns on steady. RAC-1 and RAC-2 are activated.
•
Activation of Z-5 can be indicated on NAC-2 at 20 BPM, if configured.
•
Activation of Z-6 turns NAC-1 and NAC-2 steady.