12.0

Pre-Programmed Modes

12.1
Mode 1: Agent Release, Single Hazard, Cross-zoned,
Combined Release
Out1
Signal
Steady
Out2
Signal
Escalating
Out3
Rel.
Releasing
Out4
Rel.
Releasing
RLS TMR 1 Started
RLS Tmr 1 Interrupted
RLS Tmr 1 Cancelled
RLS Tmr 2 Started
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled

12.1.1 Zone Configuration

Detection Zone -1: Alarm (Hazard Area1, Cross-zoned)
Detection Zone -2: Alarm (Hazard Area1, Cross-zoned)
Detection Zone -3: Alarm (Pressure Switch or Water-flow)
Detection Zone -4: Supervisory (Non-latching by default)
Detection Zone -5: Abort Switch
Detection Zone -6: Manual Release Switch
NAC-1: Signal, will be on steady if there is any alarm zone or manual release switch
active.
NAC-2: Signal, indicates the cadence of hazard area 1 state or supervisory circuit
(optional).
RAC-1: Releasing Circuit (Hazard Area 1)
RAC-2: Releasing Circuit (Hazard Area 1)

12.1.2 Hazard Configuration

Default Release Timer Value:
Default Manual Release Delay: 0 seconds.
Default Abort Delay Type:
Default Soak Timer Value:

12.1.3 NAC Configuration

Default Escalating NAC code of Hazard Area State:
Detection Zones
Z1
Z2
Z3
Alm
Alm
WF
X
X
X
X
Hazard Idle: Off
Hazard Alert: Temporal (see Table 7)
Phantom Zones
Z4
Z5
Z6
Zp1
Sup
AB
MR
Z1+Z2
X
(X)
X
X
X
X
X
X
X
60 seconds
Standard UL.
0 seconds
Release Timers
RT1
RT2
Zp2
Exp
Exp
Z3+Z4
X
X
69

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FR-320 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Fr-320Fr-320-wFr-320-rFr-320-drFr-320-dw

Table of Contents