12.0
Pre-Programmed Modes
12.1
Mode 1: Agent Release, Single Hazard, Cross-zoned,
Combined Release
Out1
Signal
Steady
Out2
Signal
Escalating
Out3
Rel.
Releasing
Out4
Rel.
Releasing
RLS TMR 1 Started
RLS Tmr 1 Interrupted
RLS Tmr 1 Cancelled
RLS Tmr 2 Started
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled
12.1.1 Zone Configuration
•
Detection Zone -1: Alarm (Hazard Area1, Cross-zoned)
•
Detection Zone -2: Alarm (Hazard Area1, Cross-zoned)
•
Detection Zone -3: Alarm (Pressure Switch or Water-flow)
•
Detection Zone -4: Supervisory (Non-latching by default)
•
Detection Zone -5: Abort Switch
•
Detection Zone -6: Manual Release Switch
•
NAC-1: Signal, will be on steady if there is any alarm zone or manual release switch
active.
•
NAC-2: Signal, indicates the cadence of hazard area 1 state or supervisory circuit
(optional).
•
RAC-1: Releasing Circuit (Hazard Area 1)
•
RAC-2: Releasing Circuit (Hazard Area 1)
12.1.2 Hazard Configuration
•
Default Release Timer Value:
•
Default Manual Release Delay: 0 seconds.
•
Default Abort Delay Type:
•
Default Soak Timer Value:
12.1.3 NAC Configuration
•
Default Escalating NAC code of Hazard Area State:
•
•
Detection Zones
Z1
Z2
Z3
Alm
Alm
WF
X
X
X
X
Hazard Idle: Off
Hazard Alert: Temporal (see Table 7)
Phantom Zones
Z4
Z5
Z6
Zp1
Sup
AB
MR
Z1+Z2
X
(X)
X
X
X
X
X
X
X
60 seconds
Standard UL.
0 seconds
Release Timers
RT1
RT2
Zp2
Exp
Exp
Z3+Z4
X
X