7.10

Supervised Auxiliary Power (regulated)

Supervised auxiliary power is used to power the remote annunciators and smart relay
modules. This filtered circuit is supervised therefore a short will disconnect the power and the
common trouble is active. The power is reconnected after the 'RESET' key is pressed. See
17.0 Appendix E: Specifications on page 101 for supply rating.
7.11

Unfiltered Supply (full wave rectified)

This regulated supply is not supervised. If there is a short on this circuit, the auxiliary power
does not recover automatically when the short is removed. This power supply must be
disconnected, then reconnected and the panel reset to re-establish the auxiliary power supply.
See 17.0 Appendix E: Specifications on page 101 for supply rating.