12.8.4 How the Panel Works in Mode 8

Activation of either Z-1 or Z-2 changes Hazard Area 1 state into Alarm. Release Timer 1
is started. NAC-1 turns on at Temporal. Upon the expiration of Release Timer 1, RAC-1
is active. NAC-1 turns on steady.
Activation of either Z-3 or Z-4 changes Hazard Area 2 state into Alarm. Release Timer 2
is started. NAC-2 turns on at Temporal. Upon expiration of Release Timer 2, RAC-2 is
active. NAC-2 turns on steady.
Activation of Z-6 turns both NAC-1 and NAC-2 on steady.
Activation of Z-5 can be indicated on NAC-2, if enabled.