Mode 11: Agent Release, Single Hazard, Cross-Zoned, Combined Release; Zone Configuration; Hazard Configuration; Nac Configuration - Mircom FR-320 Series Installation And Operation Manual

Pre-action/deluge and agent release control panel
Hide thumbs Also See for FR-320 Series:
Table of Contents

Advertisement

12.11 Mode 11: Agent Release, Single Hazard, Cross-zoned,
Combined Release
Out1
Signal
Steady
Out2
Signal
Escalating
Out3
Rel.
Releasing
Out4
Rel.
Releasing
RLS TMR 1 Started
RLS Tmr 1 Interrupted
RLS Tmr 1 Cancelled
RLS Tmr 2 Started
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled

12.11.1 Zone Configuration

Detection Zone -1: Alarm (Hazard Area1, cross-zoned)
Detection Zone -2: Alarm (Hazard Area1, cross-zoned)
Detection Zone -3: Alarm (Pressure Switch or Water-flow)
Detection Zone -4: Supervisory (Default non-latching)
Detection Zone -5: Abort Switch
Detection Zone -6: Manual Release
NAC -1: Signal, indicate the Hazard Area1 status.
NAC -2: Signal, indicate the Hazard Area1 status.
RAC -1: Releasing Circuit
RAC -2: Releasing Circuit

12.11.2 Hazard Configuration

Default Release Timer Value:
Default Manual Release Delay: 0 seconds
Default Abort Delay Type:
Soak Timer Value:

12.11.3 NAC Configuration

Default Escalating NAC code of Hazard Area State:
Default NAC code of supervisory is 20 BPM
88
Detection Zones
Z1
Z2
Z3
Alm
Alm
WF
X
Hazard Idle: Off
Hazard Alert: Steady
Hazard Alarm: 60BPM
Hazard Release: Steady
Phantom Zones
Z4
Z5
Z6
Zp1
Supv
AB
MR
Z1+Z2
X
(X)
X
X
X
X
X
X
X
60 seconds
Standard UL.
0 seconds (continuous)
Pre-Programmed Modes
Release Timers
RT1
RT2
Zp2
Exp
Exp
Z3+Z4
X
X

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FR-320 Series and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Fr-320Fr-320-wFr-320-rFr-320-drFr-320-dw

Table of Contents