12.11 Mode 11: Agent Release, Single Hazard, Cross-zoned,
Combined Release
Out1
Signal
Steady
Out2
Signal
Escalating
Out3
Rel.
Releasing
Out4
Rel.
Releasing
RLS TMR 1 Started
RLS Tmr 1 Interrupted
RLS Tmr 1 Cancelled
RLS Tmr 2 Started
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled
12.11.1 Zone Configuration
•
Detection Zone -1: Alarm (Hazard Area1, cross-zoned)
•
Detection Zone -2: Alarm (Hazard Area1, cross-zoned)
•
Detection Zone -3: Alarm (Pressure Switch or Water-flow)
•
Detection Zone -4: Supervisory (Default non-latching)
•
Detection Zone -5: Abort Switch
•
Detection Zone -6: Manual Release
•
NAC -1: Signal, indicate the Hazard Area1 status.
•
NAC -2: Signal, indicate the Hazard Area1 status.
•
RAC -1: Releasing Circuit
•
RAC -2: Releasing Circuit
12.11.2 Hazard Configuration
•
Default Release Timer Value:
•
Default Manual Release Delay: 0 seconds
•
Default Abort Delay Type:
•
Soak Timer Value:
12.11.3 NAC Configuration
•
Default Escalating NAC code of Hazard Area State:
•
•
•
•
•
Default NAC code of supervisory is 20 BPM
88
Detection Zones
Z1
Z2
Z3
Alm
Alm
WF
X
Hazard Idle: Off
Hazard Alert: Steady
Hazard Alarm: 60BPM
Hazard Release: Steady
Phantom Zones
Z4
Z5
Z6
Zp1
Supv
AB
MR
Z1+Z2
X
(X)
X
X
X
X
X
X
X
60 seconds
Standard UL.
0 seconds (continuous)
Pre-Programmed Modes
Release Timers
RT1
RT2
Zp2
Exp
Exp
Z3+Z4
X
X