Command Menu/Dialer-Config/Time
Parameter
2. Cellular report date
Cellular Report Date
0
Command Menu/Dialer-Config/Time
Parameter
3. Auto test time
Auto-Test (HH:MM):
00:30
Command Menu-->Dialer-Config
i
Note:
10.10.5 Dialer Enable/Disable
Dialer Ena/Dis
[X] ENABLE
------WARNING-----
Dialer Disabled!!!
64
0 ->Default
The cellular report
date ranges from 0 to
28
00:30 ->Default
Refer to 10.3 How to Use the Keypad to Program the FR-320 on page 49 for
detailed instructions on making menu selections.
[X] ENABLE ->Default
[ ] DISABLE
Use this function to set the test report date
for the cell phone setup. If the date is set to
0, this means there is no test reporting for
cell phone or the phone line is a regular line.
Other settings could be anywhere from 01-
28, representing which day of the month the
test should be performed. Press the UP or
DOWN buttons to scroll through the days.
Use this function to set the time for auto test.
This test has to be performed once a day to
send the test report to the monitoring station.
The time is in 24hr format, which means
00:30 is 30 minutes after mid-night. Press
the UP or DOWN buttons to increase or
decrease the time.
Please do not use the following test
times: 00:00, 01:55, 02:00 and 03:00.
The dialer is enabled by default. When the
dialer is enabled or disabled, a warning
message appears.
Warning: The dialer cannot report any event
to the monitoring station if it is disabled.
Configuration
Need help?
Do you have a question about the FR-320 Series and is the answer not in the manual?
Questions and answers