Mircom FR-320 Series Installation And Operation Manual page 54

Pre-action/deluge and agent release control panel
Hide thumbs Also See for FR-320 Series:
Table of Contents

Advertisement

Command Menu-->Panel Config-->Features
1. Manual Sig. Silence
Man. S i g. S i l.
[X ] EN AB LE
Command Menu-->Panel Config-->Features
2. Wtr/Sprk. Retd
W a t e r f lo w/S p r k R e t d
[X ] D I S AB LE
Command Menu-->Panel Config-->Features
3. Aux Dis Corr
Au x D i s. D i s C o rr
[X ] EN AB LE
Command Menu-->Panel Config-->Features
4. Sig-Sil Inh Tmr
S i g - S i l . I n h i b i t T i me r
[X ] D I S AB LE
Command Menu-->Panel Config-->Features
5. Aux. Dis. Dis Alam&Sv
Aux Dis. Dis Alm&Sv
[X ] D I S AB LE
Command Menu-->Panel Config-->Features
6. Auto Sig-Sil. Tmr
Au to S i g-S i l. Tm r
[X ] D I S AB LE
Command Menu-->Panel Config-->Features
7. Rem. Annun.
N o. o f R e m o t e A n n u n.
[X ] N ON E
54
[X] ENABLE ->Default
[ ] DISABLE
[ ] ENABLE
[X] DISABLE->Default
[X] ENABLE ->Default
[ ] DISABLE
[X] DISABLE->Default
[ ] 10sec
[ ] 20sec
[ ] 30sec
[ ] 1min
[ ] ENABLE
[X] DISABLE->Default
[X] DISABLE->Default
[ ] 5 Min
[ ] 10 Min
[ ] 20 Min
[ ] 30 Min
[X] NONE->Default
[ ] 1
[ ] 2
...
[ ] 6
Configuration
Use this function to enable or
disable the Signal Silence
operation on the panel.
By default all the initiating circuits
configured as waterflow or
sprinkler act as non-verified
alarms. If enabled, a retard
operation is performed for initiating
circuits configured as waterflow or
sprinkler.
By default this function will
disconnect the auxiliary alarm
relay when the aux disconnect
button is pressed. If enabled, this
function will disconnect the
auxiliary alarm relay and all
correlated relays when the aux
disconnect button is pressed.
Correlated relays include: RM-
306 and SRM-312.
Use this function to inhibit the
signal silence switch for a desired
length of time. The time period
should expire before the signals
may be silenced. According to the
Canadian National Building Code,
this timer should be set to one
minute.
If enabled the Common Alarm and
Common Supervisory relays will
be disconnected when Aux.
Disconnect is pressed. Also, the
PR-300 will not transmit a
supervisory or alarm event.If
disabled, the Aux disconnect
switch has no effect on the
Common Alarm relay, the
Common Supervisory relay, and
the PR-300.
Use this function to set the time
period for which the indicating
circuits will sound before they are
automatically silenced. For
Canadian installations, disable the
Auto Signal Silence Timer.
Use this function to program the
number of remote annunciators.
Any combination of remote
annunciators or smart relays can
be used as long as the number
does not exceed 6. The
annunciators' addresses should be
linear: without gaps and in
sequence.