16.4.4

Control via Remote Contacts

In the operation mode
is controlled via the control word in PZD1, with the bits 0 to 9 corresponding to the contact inputs
S1IND to S6IND, multifunctional input MFI1D and the inputs EM-S1IND to EM-S3IND of an expansion
module.
In the use of the remote contacts, the frequency inverter behaves in the same way as in control via
the hardware contact inputs. The meaning of these inputs can be taken from the operating
instructions.
Note:
Release is only possible if the hardware release is available via the digital inputs STOA and
STOB.
State machine:
The values displayed in the states are reflected in the status word (Bit 0 to 6) in PZD1.
Note:
The inputs set via the control word can be observed with the help of parameter
Inputs
release is available and the control word/Bit 0 has been set.
If the data set switch-over is used, please make sure that parameter
set to operation mode "2 – Control via remote contacts" in all the data sets used.
50
Local/Remote
412 = "2 - Control via remote contacts", the frequency inverter
Power-On
Initialization
Switched On
0x23
Enable
Enable
Off
On
Operation
enabled
0x27
250. Digital input "Inverter Release" is only displayed as being set if the hardware
Profibus DP V1 Agile
Fault ack.
Fault
0x08
from any state
Handling of the Objects
Digital
Local/Remote
412 is
06/2010