BONFIGLIOLI Vectron Agile Series Communications Manual page 21

Profibus
Table of Contents

Advertisement

Setting PPO Type
The six possible objects PPO1 to PPO4, PKW and PZD are available in the ACU/AGL-DPV1 menu.
The desired object can be assigned to the frequency inverter using drag and drop.
The screen copy from the STEP7 Hardware Configurator shows a frequency inverter with Station
Address 3 and a customer-specific configuration.
The above configuration setting is:
1 PKW Object
4 PZD Objects
Note:
− The data direction IN/input and OUT/output is from the master's point of view.
− Every single configured PZD object results in two word (4 byte) objects PZDn PZDn+1
for both input and output.
− The CM-PDPV1 offers four predefined objects (PPO1...4) to be compatible to the former
CM-PDP and two additional objects PKW (communication channel) and PZD (process
data) for application specific configurations.
Restrictions for user defined configuration settings:
− The PKW object is allowed only once as the first object.
− As a minimum one PZD object must be configured.
− The resulting number of all objects must be less than or equal to 36 bytes (18 words).
Note:
A restriction violation results in a configuration error message from the PLC on the Profibus
start up cycle. Also the Operation Mode Led on the CM-PDPV1 flashes red (2 flashes).
06/2010
8 bytes or 4 words, communication objects (input/output)
16 bytes or 8 words, process data objects (input/output)
Profibus DP V1 Agile
21