Example:
DP-Master OUT
Parameter
= C: 6 480 I: 0300 V: -005500 000F 2000 0000 0000 0000 0000
C: 6
C: 480
I: 0300
V: -005500
000F
2000
0000
0000
0000
0000
DP-Master IN
Parameter
= C: 5 480 I: 03 00 V: -005500 06A7 2000 1147 0CCC 0800 0000
C: 5
C: 480
I: 03 00
V: -005500
06A7
2000
1147
0CCC
0800
0000
56
Actual Value
281
Meaning
Request identification = 6 (Read parameter value Array)
Parameter number = 480 (Fixed frequency 1)
Data set = 3
Parameter value = -5500 = -55.00 Hz (0xFFFEA84 hexadecimal)
Release command (transition 4)
Set point = 0x2000 = 50% of the reference value
not used
not used
not used
not used
Actual Value
284
Meaning
Reply identification = 5 (Transmit parameter value long Array)
Parameter number = 480 (Fixed frequency 1)
Data set = 3
Parameter value = -5500 = -55.00 Hz (0xFFFEA84 hexadecimal)
State = 0x27 "Operation enabled" (Bit 0 ... 6),
Warning 2 present (Bit 15 = 1 threat of fault switch-off),
reference value reached (Bit 10 = 1),
remote operation (Bit 9 = 1),
Warning present (Bit 7 = 1)
Actual value = 0x2000 = 50% of the reference value
Abs. current = 0x1147 = 27% of the rated motor current
Active current = 0x0CCC = 20% of the rated motor current
Warning, Warning motor temperature available