BONFIGLIOLI Vectron Agile Series Communications Manual page 55

Profibus
Table of Contents

Advertisement

Handling of the Objects
The following diagrams show the display for a configuration setting with PPO2. The PPO2 includes the
communication PKW channel for parameter access and 6 PZD objects with default settings for In-PZD
objects.
DP-Master OUT
Parameter
= C: a nnnn I: iiii 00 V: wwwwww cccc rrrr xxxx xxxx xxxx xxxx
C: a
a
C: nnnn
nnnn = parameter number
I: iiii
iiii
V: ww..w ww..w = parameter value
cccc
PZD1 = control word
rrrr
PZD2 = reference value
xxxx
PZD3 user defined
xxxx
PZD4 user defined
xxxx
PZD5 user defined
xxxx
PZD6 user defined
DP-Master IN
Parameter
= C: a nnnn I: iiii 00 V: wwwwww cccc ssss xxxx xxxx xxxx xxxx
C: a
a
C: nnnn
nnnn
I: iiii
iiii
V: ww..w
ww..w = parameter value
cccc
PZD1
ssss
PZD2
xxxx
PZD3
xxxx
PZD4
xxxx
PZD5
xxxx
PZD6
06/2010
Actual Value
281
Meaning
= request identification hexadecimal
= index
Actual Value
284
Meaning
= reply identification hexadecimal
= parameter number decimal
= index
= state word
= actual value
= abs. current
= active current
= Warning
= Fault
Profibus DP V1 Agile
decimal
hexadecimal
decimal (with sign in front)
hexadecimal
hexadecimal, relative to
0x4000 = 100% of the reference value
hexadecimal
hexadecimal
hexadecimal
hexadecimal
hexadecimal
decimal (with sign in front)
hexadecimal
hexadecimal, relative to
0x4000 = 100% of the reference value
hexadecimal, relative to 0x4000 =
100% of the rated motor current
hexadecimal, relative to 0x4000 =
100% of the rated motor current
hexadecimal (bit-coded)
hexadecimal
55