3. Press the ENTER key
4. Press the UP ARROW key to access the analog output calibration
5. Press the ENTER key
You may measure the output of the analog output during the calibration procedure. Likewise during the
calibration the analog output is active and should be seen by your PLC/SCADA system.
6. Use the UP and DOWN arrow keys to adjust the output signal as required. The value displayed on the
screen may not match the actual output signal and is for visual reference only.
7. Press the ENTER key once more to accept the calibration
8. Use the UP and DOWN arrow keys to adjust as in step 6 above
9. Press the ENTER key once more to accept the calibration value
10. Analog output signal calibration is complete
11. Press the MENU key three times to exit back to the main operating screen
This indicates that the output current for 0% speed has been set greater than or equal to the output current setting for
100% speed. Repeat the process and ensure that the 0% calibrated signal is set to a value lower than the 100%
calibrated signal.

8.2 PulsaGuard Pump Protection

PulsaGuard is designed to turn your pump off when running in dangerous conditions. These conditions are user
configurable and can be easily modified to meet each application.
C A L I B R A T I O N
C A L I B R A T I O N
P U M P F L O W
C A L I B R A T E D
A N A L O G O U T P U T
S E T 0 % S P E E D T O
4 . 0
M A
S E T 1 0 0 % S P E E D T O
2 0 . 0
A N A L O G O U T P U T
C A L I B R A T E D
If you receive the following message:
C U R R E N T D E L T A
O U T O F R A N G E
52
M A