Putting It All Together To Run The Mpc Vector - Idex Pulsafeeder MPC Vector Installation, Operation & Maintenance Manual

Universal control for pulsa and eclipse. suitable for any gear, reciprocating or positive displacement pumps.
Table of Contents

Advertisement

22.4

Putting it all together to run the MPC Vector

The proportional, integral, and differential components are all added together into a command sum which is used to
set the motor speed. The motor speed command does have software protection which prevents the motor speed from
ever exceeding the max motor speed or from being negative and therefore if the command loop is unstable, no
damage can be caused to the drive, motor, or pump. Please be aware though that the motor could reach maximum
speed during tuning and all necessary system precautions should be taken.
Also note that the differential part alone cannot be used to start the motor since it depends on previous values. If the
previous saved error matches the current error then the differential part will be 0 and therefore the differential part
alone will not start the motor reliably. It is possible to eliminate one of the parts by setting the appropriate coefficient
to 0 (i.e. if you want a PI only controller set Kd to 0 to eliminate the differential part). However the tuning steps
below assume that all 3 parts will be used.
Step 1 – Configure the MPC Vector (reference earlier sections of this IOM for more detail)
1. Make sure that the chosen flow meter is hooked up to the proper location in the MPC Vector.
2. Flow units should be set appropriately in the menu
3. Max flow should be set to at least the max flow achievable by the pump at max speed.
4. Flow sensor type should be set appropriately (digital or analog)
5. Flow calibration should be performed to make sure the MPC Vector flow reading matches flow meter
feedback.
Step 2 – Choosing the test set point
In order to tune the PID loop it is necessary to choose a test speed. For most purposes the test flow should be set to
approximately 80 – 85% of the max flow. If the test point is too close to the maximum flow, you may not notice the
overshoot. If the test point is too low you may have an unstable system at higher flow rates.
Step 3 – Tune the Proportional gain
1. Start with an integral gain of 0 and a derivative gain of 0. The proportional gain should be set to allow the
motor to start reliably.
2. Set the motor to the test set point
3. Start with a proportional gain of 0.1
4. Make sure that the integral and differential gains are 0
5. At the main operations mode screen, attempt to start the pump. If the motor starts and settles at a low speed
with minimal flow then the proportional gain is set. If not, increase the gain by 0.05 and try again. Continue
until motor start condition is met reliably.
Step 4 – Tune the Integral gain
1. The Integral gain is what will ultimately pull the speed up to the desired set point. Note that because the
Integral gain is based on a sum it takes some time for the Integral part to stabilize.
2. Make sure that the proportional gain is set as found above. differential gain is still 0
3. Start with an integral gain of 0.05
4. At the main operations mode screen, start the pump. You should see that the flow is now slowly building
towards the set point. Increasing the integral gain will cause the buildup to occur faster. Keep adding 0.05 to
the integral gain until you overshoot your set point. As an example, if your set point is 5 GPM, your gain
might go to 5.1 GPM before falling down to 4.9 GPM or so and oscillate for a few seconds.
104

Advertisement

Table of Contents
loading

Table of Contents