230 VAC Models - Single and Three Phase
See Table 5-1 Sizing Branch Circuits (208/230VAC) below for recommended wire and circuit breaker
sizing information.
Power
Requirements
Actual
Draw
MPC VECTOR
10.6 A
and 1.0 Hp motor
MPC VECTOR
14.8 A
and 2.0 Hp motor
MPC VECTOR
19.7 A
and 3.0 Hp motor
MPC VECTOR
---
and 5.0 Hp motor
Figure 5-5 MPC VECTOR Product Label
Recommended Minimum Wiring and Circuit Breaker
Single Phase 208/230 VAC
Circuit
Wire
Breaker
Size
15 A
14 AWG
2.0 mm
20 A
12 AWG
3.5 mm
25 A
12 AWG
3.5 mm
---
---
Table 5-1 Sizing Branch Circuits (208/230VAC)
19
Three Phase 208/230 VAC
Wire
Actual
Circuit
Size
Draw
Breaker
2
5.8 A
10 A
2
9.1 A
15 A
2
12.4 A
20 A
---
19.6 A
25 A
Wire
Wire
Size
Size
2
14 AWG
2.0 mm
2
14 AWG
2.0 mm
2
12 AWG
3.5 mm
2
12 AWG
3.5 mm