3. Press the ENTER key
4. Press the DOWN arrow key once, to access the analog input calibration
5. Press the ENTER key
6. Press the ENTER key
7. Apply your desired maximum mA control signal to the MPC VECTOR (usually 20 mA)
8. Press the ENTER key
(The lower line shows the flow or speed set point the MPC VECTOR will use for this signal value)
9. Press the UP and DOWN arrow keys to change the Speed/Flow corresponding to the Analog Input Value.
10. Press the ENTER key once more to accept the calibration value
11. Apply your desired minimum mA control signal to the MPC VECTOR (usually 4 mA)
12. Press the ENTER key
(The lower line shows the setting the MPC VECTOR will use for this signal value)
13. Press the UP and DOWN arrows to adjust the Speed/Flow corresponding to the Analog Input value.
14. Press the ENTER key once more to accept the calibration value
15. Analog input signal calibration is complete
16. Press the MENU key three times to exit back to the main operating screen.
- M E N U -
C A L I B R A T I O N
C A L I B R A T I O N
P U M P F L O W
C A L I B R A T I O N
A N A L O G I N P U T
A N A L O G I N P U T
W E T C A L
A P P L Y M A X M A
E N T E R T O S T A R T
M A X S E T P T
F L O W
(The mA value will be equal to your signal source/calibrator level)
A P P L Y M I N M A
E N T E R T O S T A R T
M I N S E T P T 4 . 0 M A
F L O W
(The mA value will be equal to your input signal level)
A N A L O G I N P U T
C A L I B R A T E D
2 0 . 0 M A
2 5 . 0 0 G P H
2 . 5 0 G P H
48