Idex Pulsafeeder MPC Vector Installation, Operation & Maintenance Manual page 100

Universal control for pulsa and eclipse. suitable for any gear, reciprocating or positive displacement pumps.
Table of Contents

Advertisement

Drive module display reads "CL"
Drive module display reads "nld"
Drive module display reads "HF" or
"LF"
Drive module display reads "PF"
Drive module display reads "F1-F9"
Problem
Potential Cause
No Display
No power supplied.
Back-lighting
Supply power wired incorrectly.
Supply power outside of specification.
No Text on
Contrast out of adjustment.
Display
Software did not initiate properly.
No power
No power supplied.
Indicators
Supply power wired incorrectly.
Supply power outside of specification.
DRIVE ERRORS AND FAULTS
Drive has gone into a current limit
mode to protect the pump motor.
An attempt was made to start the
controller prior to calibrating the pump
motor.
The AC drive DC bus is to high (HF) or
the DC bus is too low (LF)
Current Overload has occurred and
drive shuts down.
Drive has internal fault.
Solution
DISPLAY
Check power source. plug & circuit breaker
Check wiring.
Check voltage/frequency against specification.
Adjust as per section 8.4
Remove and re-apply AC power
POWER
Check power source. Plug & Circuit Breaker
Check wiring.
Check voltage/frequency against specification.
94
Check for pump binding or drive/ motor
combination being undersized.
Perform a motor calibration as outlined
in Section 6.4 Motor Parameter Setup
Check incoming line voltages for proper
input tolerances. See Section 13
Specifications for input tolerances.
Check pump for binding or mechanical
failure.
Consult factory