Wiring Rules - Siemens SIMATIC ET 200SP System Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Wiring

5.5 Wiring rules

5.5
Wiring rules
Wiring rules
Wiring rules for ...
Permitted cable cross-sections of solid cables
Permitted cable
Without wire end ferrule
cross-sections of
flexible cables
With wire end ferrule (with
plastic sleeve)
With TWIN wire end fer-
rule
Stripping length of the wires
Wire end ferrules in accordance with DIN 46228
with plastic sleeve
***
* AWG: American Wire Gauge
** Wire end ferrules without plastic sleeve: 0.25 to 2.5 mm
*** See note on Wire end ferrules
Note
Wire end ferrules
Optimum results with respect to a high-quality and permanent electrical connection with
maximum conductor pull forces at the same time can be achieved by using crimping dies,
preferably with smooth surfaces, which are provided, for example, with rectangular and
trapezoidal crimp cross-sections.
Due to the large number of crimping dies used in the industry, we can recommend others on
request. Crimping dies with a pronounced wave profile are unsuitable.
60
***
***
CPU/interface module (supply
voltage)
0.2 to 2.5 mm
2
AWG
: 24 to 13
*
0.2 to 2.5 mm
2
AWG
: 24 to 13
*
0.25 mm to 1.5 mm
2**
AWG
: 24 to 16
*
0.5 mm to 1 mm
2
AWG
: 20 to 17
*
8 to 10 mm
8 and 10 mm long
/AWG: 24 to 13
2
BaseUnits
(push-in terminal)
AWG*: 24 to 14
0.14 mm to 1.5 mm
2
AWG
: 26 to 16
*
0.5 to 0.75 mm
(see below)
2
AWG
: 20 to 18
*
Distributed I/O system
System Manual, 12/2015, A5E03576849-AF