Commissioning procedure
For commissioning of the ET 200SP distributed I/O system as an I-device on the
PROFINET IO, we recommend the following procedure:
Table 10- 2
Step
1
2
3
4
5
6
7
8
9
10
Distributed I/O system
System Manual, 12/2015, A5E03576849-AF
Procedure for commissioning the ET 200SP as an I-device on the PROFINET IO
Procedure
Installing ET 200SP
Connecting ET 200SP
Supply voltages
PROFINET IO
Sensors and actuators
Inserting a SIMATIC memory card in the I-device
Configuring the I-device
Switching on supply voltages for the IO controller
Switching on supply voltages for I-device and IO
devices
Download configuration to the I-device
Switching IO controller and I-device to RUN
mode
Checking LEDs
Testing inputs and outputs
10.2 Commissioning the ET 200SP for PROFINET IO
See ...
Section Installation (Page 39)
Section Wiring (Page 49)
Section Removing/inserting a
SIMATIC memory card on the CPU
(Page 180)
Section Configuring (Page 97)
Documentation of the IO controller
CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
00) manual and documentation of
the IO devices
STEP 7 online help
Documentation of the IO controller
and CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
00) manual
CPU 15xxSP-1 PN
(http://support.automation.siemens
.com/WW/view/en/90466439/1333
00) manual
The following functions are helpful:
Monitoring and modifying tags,
testing with program status, forc-
ing, controlling the outputs. See
section Test functions and elimi-
nating problems (Page 224)
Commissioning
173