Configuring - Siemens SIMATIC ET 200SP System Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

9.1

Configuring

Requirements
Configuration control is supported by the ET 200SP distributed I/O system with both an ET
200SP CPU and with interface modules via PROFINET IO and PROFIBUS DP.
Centrally for ET 200SP CPU:
● STEP 7 Professional V13 Update 3 or higher
● CPU 1510SP-1 PN/CPU 1512SP-1 PN
● Firmware version V1.6 or higher
● All modules of the CPU must be able to start up even with different configurations.
– The startup parameter "Comparison preset to actual configuration" of the CPU is set to
– The module parameter "Comparison preset to actual module" for the module is set to
Distributed via PROFINET IO:
● Engineering Tool (e.g. STEP 7)
● IM 155-6 PN BA/ST/HF
● You have assigned the interface module to an IO controller.
Distributed via PROFIBUS DP:
● Engineering Tool (e.g. STEP 7)
● IM 155-6 DP HF
● You have assigned the interface module to a DP master.
● The startup parameter is set to "Operate if preset configuration does not match actual
configuration"
Distributed I/O system
System Manual, 12/2015, A5E03576849-AF
"Startup CPU even if mismatch" (default setting) and the module parameter
"Comparison preset to actual module" of the module is set to "From CPU" (default
setting).
or
"Startup CPU even if mismatch".
Configuration control (option handling)
9.1 Configuring
145