9.2.3

Control data record for an interface module

Slot assignment
The following table shows the possible slots for the various modules for an
ET 200SP interface module:
Table 9- 3
Slot assignment
Modules
Interface module
Station extension
BA-Send
ET 200SP I/O module
Server module
ET 200AL I/O module
Distributed I/O system
System Manual, 12/2015, A5E03576849-AF
Possible slots
0
1
1 - 12
for IM 155-6 PN BA
1 - 32
for IM 155-6 PN ST,
IM 155-6 DP HF
1 - 64
for IM 155-5 PN HF
1 - 13
for IM 155-6 PN BA
1 - 33
for IM 155-6 PN ST,
IM 155-6 DP HF
1 - 65
for IM 155-5 PN HF
34 - 49 for IM 155-6 DP HF
66 - 81 for IM 155-6 PN ST,
IM 155-6 PN HF
Configuration control (option handling)
9.2 Creating the control data record
Comment
The interface module (slot 0) is not an element of the configu-
ration control, but instead controls this.
For mixed configuration with ET 200AL modules, BA-Send is
always on slot 1.
Downstream from the interface module
The server module completes the configuration of the
ET 200SP station after the last I/O module.
For mixed configuration with ET 200AL modules