3.2

Hardware configuration

Maximum mechanical configuration
As soon as one of the following rules applies, the maximum configuration of the ET 200SP
has been reached:
Table 3- 2
Properties
Number of modules
Backplane bus length of the
ET 200SP
Maximum electrical configuration
The number of operable I/O modules of a potential group is limited by the
● Power consumption of the I/O modules
● Power consumption of the components supplied via these I/O modules
The maximum current-carrying capability of the terminals on the BaseUnit L+/ground is 10 A.
Address space
The address space depends on the CPU/interface module (see CPU
(http://support.automation.siemens.com/WW/view/en/90466439/133300) Manual) and the
interface module used (see Interface module
(http://support.automation.siemens.com/WW/view/en/55683316/133300) Manual):
● For PROFINET IO: dependent on the IO controller/IO device used
● For PROFIBUS DP: dependent on the DP master used
Distributed I/O system
System Manual, 12/2015, A5E03576849-AF
Maximum mechanical configuration
Rule
Maximum 12/32/64 I/O modules (depending on the
CPU/interface module used, see CPU
(http://support.automation.siemens.com/WW/view/en/9046643
9/133300) and Interface module
(http://support.automation.siemens.com/WW/view/en/5568331
6/133300) Manual)
The maximum configuration is reduced by 1 module for each
6 F-modules F-RQ 1x24 VDC/24..230VAC/5A (6ES7136-
6RA00-0BF0).
maximum 1 m mounting width (without CPU/interface module,
including server module)
Application planning
3.2 Hardware configuration
31