Operating Instructions
Manual paralleling
+
CB 1
-
Manual paralleling
+
CB 2
-
See section 5.5 "Use of the automatic synchronizing device as synchrocheck" for
Note
parameter settings for operation as synchrocheck.
5.4.2
Assigning one parameter set to several paralleling points
This case applies if, for example, several identical circuit breakers/generators are
paralleled under the same conditions.
Example: One parameter set is assigned to two paralleling points :
A signal which activates parameter set 1 is permanently present at input IN1. If a signal
is applied to input IN2 before Start, paralleling point 1 is activated, a signal at IN3 selects
paralleling point 2.
Programming:
Parameter I1 = I8
Parameter I2 = 1
Parameter I3 = 2
Parameter O2 = 1
Parameter O3 = 2
Operating behaviour:
Signal to:
Inputs IN1 and IN2
Inputs IN1 and IN3
5.4.3
Further configuration options
When the inputs and outputs are not used for selecting parameter sets and paralleling
points, they can be used for other functions e.g. for signaling or additional control
commands (see tables in section 4.2.8 from value 15 on).
abb
ABB Switzerland Ltd
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
switch
-
switch
CB 1
-
CB 2
MAN
Outputs:
OUT2 closes
OUT3 closes
Document No Art Part
SYN 520X
-X12:8
-X12:9
OUT 7
-X12:7
-X6:1
COMMAND
-X6:2
-X10:1
IN 1
-X10:2
-X10:3
IN 2
-X10:4
-X10:13
IN 7
-X10:14
Selected:
Parameter set 1 and paralleling point 1
Parameter set 1 and paralleling point 2
3BHS109762 E01
SYN 5201/SYN 5202
-X11:1
OUT 1
-X11:2
-X11:3
OUT 2
-X11:4
S00018
Language
Revision
page
en
D
71
+