Test functions
Code
Description
124
Voltage adjusting
command has no effect
125
Frequency adjusting
command has no effect
126
Possible range for ton
exceeded
127
Test function is active
128
Result of the test function
is not plausible
abb
ABB Switzerland Ltd
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
Remarks
The measured value for
dU/dt was less than
0.1 %/s
The message is also
displayed if
TEST U-Match is still set
to ON and another test
function is to be carried
out
The measured value for
df/dt was less than
0.05 %/s. The message
is also displayed if
TEST f-Match is still set
to ON and another test
function is to be carried
out
The measured value
must lie between 0 and
1 s. The message is
also displayed if
TEST ton is still set to
ON and another test
function is to be carried
out
One or more test
functions TEST ton,
TEST U-Match or
TEST f-Match of the
current parameter set
was still set to ON, while
trying to set the device
to READY.
The result calculated by
the test function lies
outside of the settable
range. This is
determined by the
maximum and minimum
value of the
corresponding
parameter
Document No Art Part
3BHS109762 E01
SYN 5201/SYN 5202
Remedy
Check whether:
adjusting commands are
effective (LED, relay contacts,
ext. circuits to voltage
regulator)
adjusting commands act in the
right direction
measuring voltages are
permanently present during the
test function
Check whether:
adjusting commands are
effective (LED, relay contacts,
external circuits to governor)
adjusting commands act in the
right direction
measuring voltages are
permanently present during the
test function
Check whether the paralleling
commands are effective (LED,
relay contacts, ext. circuits to
circuit breaker)
Dual channel systems: The
series-connected second
channel must be bridged,
ideally by applying the release
dead bus signal
See section 4.2 for correct
handling of the test function
Set test function to OFF
and confirm (!)
&
, then set device to
DATA
READY
See section 4.2
Language
Revision
en
page
D
107