2. SYNCHROTACT 5 is not in error status, but the synchronizing process cannot be
started, takes a very long time or paralleling does not take place:
1. SYNCHROTACT 5 is blocked: the BLOCKED LED lights up: the device is not
ready for operation (e.g. following manipulation of the settings) or TEST mode is
selected (only possible with the "7 parameter sets" option)
2. SYNCHROTACT 5 is ready (READY LED) or in operation (OPERATING LED):
temporarily set parameter t tot to a low value (e.g. 1 minute). On a further
attempt, the synchronizing process will be aborted after the set time. Read error
codes from the LCD or using SynView and proceed in accordance with section
9.2.3
3. Faults in connection with a communication interface: refer to section 9.3
If this advice does not lead to success, proceed in accordance with section 9.2.4.
9.2.3
Fault and event table
On the LCD, the code of the last detected fault is displayed. A description of the codes
can be found in the following table. "Older" faults can be viewed using the keypad. In the
case of devices without a built-in control unit, in the event of a fault the error messages
can be read out in plain text using the PC tool SynView .
Events
Code
Description
001
Auxiliary voltage on
003
SYNCHROTACT selected
004
SYNCHROTACT stopped
005
Device ready
006
Device not ready
011
Data change
021
Adjusting command U+
022
Adjusting command U-
023
Adjusting command f+
024
Adjusting command f-
025
Release contact closes
026
Release contact opens
027
Paralleling command
contact closes
028
Paralleling command
contact opens
029
Blocking active
030
Blocking cancelled
031
Operating control interface
blocked
abb
ABB Switzerland Ltd
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
Remarks
After the electronics power supply is connected
After the Start pulse
After the Stop pulse
SYNCHROTACT 5 is ready for operation
SYNCHROTACT 5 is blocked.
without error = service operation; with error = fault
This event is displayed when the device changes from READY
or OPERATING status into BLOCKED status, i.e. following a
write or blocking command
Higher voltage adjusting command
Lower voltage adjusting command
Higher frequency adjusting command
Lower frequency adjusting command
Output contact of channel 2 (synchrocheck)
Output contact of channel 2 (synchrocheck)
Issue of a paralleling command by the command generation
(in synchrocheck mode: paralleling release)
End of the paralleling command (in synchrocheck mode : end
of paralleling release)
Blocking signal to one of the configurable inputs has
interrupted synchronizing process.
Blocking signal has released the synchronizing process again.
Input BLK REM active; local control only
Document No Art Part
3BHS109762 E01
SYN 5201/SYN 5202
Language
Revision
page
en
D
102