10.3
Interfaces
10.3.1
Service interface
Ethernet for SynView
Bridgeable distance
10.3.2
Interface for time synchronization
Time synchronization RS232
Pin assignment
10.3.3
Operating interface
Modbus RTU
Pin assignment:
The transmission medium for the Modbus RTU connection
is a two-wire twisted copper cable.
Profibus DP
Pin assignment:
The transmission medium for the Profibus DP connection is
a two-wire twisted copper cable.
Lon-Bus
The optical fibre connection is made using the following
pair of connectors:
LWL-Anschluss
abb
ABB Switzerland Ltd
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
Service-Taster
Document No Art Part
3BHS109762 E01
SYN 5201/SYN 5202
100 m
2: TXD (not connected)
3: RXD
5: GND
1: DE [RS485]
2: RS232-RX
3: RS232-TX
4: +5 V bus
5: Ground bus
6: RS485 A-line
7: RS485 B-line
8: Not used
9: Not used
PE: Shield
1: Not used
2: Not used
3: B-line
4: RTS (Request to send)
5: Isolated Ground bus
6: Isolated +5 V bus
7: Not used
8: A-line
9: Not used
PE: Shield
HFBR-2412 and
HFBR-1414
LEDs