Operating Instructions
4.2.8
Configuration parameters (Option)
Digital inputs I1 to I7 and digital outputs O1 to O7
Normally, the configuration is fixed prior to commissioning. The settings are therefore
based on the project planning data.
The following table shows all possible functions for the inputs :
Setting
Function
value
±1 ***
Paralleling point 1 and Parameter set 1
±2
Paralleling point 2 and Parameter set 2
±3
Paralleling point 3 and Parameter set 3
±4
Paralleling point 4 and Parameter set 4
±5
Paralleling point 5 and Parameter set 5
±6
Paralleling point 6 and Parameter set 6
±7
Paralleling point 7 and Parameter set 7
±8
Parameter set 1
±9
Parameter set 2
±10
Parameter set 3
±11
Parameter set 4
±12
Parameter set 5
±13
Parameter set 6
±14
Parameter set 7
±15
Selection of TEST mode
±16
Blocking of synchronizing process
±17
Blocking of synchronizing process delayed by
t block
±18
Stop synchronization
±19
Start synchronization
±20
Cancel fault and set device to "Ready"
±21
No function
±22
No function
±23
No function
±24
No function
±25
No function
±26
No function
±27
No function
±28
No function
±29
No function
±30
No function
±31
No function
±32
No function
*** The "+" in front of the setting value indicates that the related function via operating
Note
control interface will be blocked as long as the blocking input "BLK REM" is active. A "-"
in front of the setting value indicates that blocking of the function is disabled not (see
section 5.6.2).
abb
ABB Switzerland Ltd
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
Remarks
The parameter set is only selected if no other
input programmed with values from 8 to 14 is
active.
These programming settings are only required if
the number of parameter sets and the number of
paralleling points differ.
(see examples in section 5.4)
Normal synchronizing, but the paralleling relay is
not operated. A configurable output relay with the
value 16 can be used in its place (see below).
A running synchronizing process is stopped and
is continued when the signal is dropped.
A running synchronizing process is stopped. After
the signal is dropped, the time t block elapses,
then the synchronizing process is automatically
continued.
Second Stop command
Second Start command
If an error is detected, the device automatically
changes to the status 'Blocked with error'. This
function can be used to cancel the error and
return the device to readiness for operation.
Document No Art Part
3BHS109762 E01
SYN 5201/SYN 5202
Language
Revision
page
en
D
47