Operating Instructions
4.3.3
Addressing Profibus DP
28 words, each with 16 bits, are transmitted. The addressing is as follows:
Add-
Content
ress
1
Digital inputs
2
Digital outputs
3
Digital outputs
4
5
Actual value 
6
Actual value s
7
8
9
10
11
Actual value ds/dt
12
Back-indication
parameter set
13
Software version
Command counter reading parameter set 1
14
Command counter reading parameter set 2
15
Command counter reading parameter set 3
16
17
Command counter reading parameter set 4
Command counter reading parameter set 5
18
Command counter reading parameter set 6
19
Command counter reading parameter set 7
20
21
Current event (event code)
22
Year of the current event
23
Month of the current event
24
Day of the current event
25
Hour of the current event
26
Minute of the current event
27
Second of the current event
28
Hundredth of a second of the current
event
*
read = read data from SYNCHROTACT 5
**
signed integer = whole numbers
***
unsigned integer = positive whole numbers
abb
ABB Switzerland Ltd
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
Word type
Bit-coded
Bit-coded
Bit-coded
Analog value
Analog value
Analog value
Analog value
Analog value
Analog value
Analog value
Analog value
of
selected
Analog value
Analog value
Analog value
Analog value
Analog value
Analog value
Analog value
Analog value
Analog value
Analog value
Analog value
Analog value
Analog value
Analog value
Analog value
Analog value
Analog value
Document No Art Part
Direction
Format
of
trans-
mission
read and
--
write*
read
--
read
--
read
signed integer**
read
signed integer
read
signed integer
read
signed integer
read
signed integer
read
signed integer
read
signed integer
read
signed integer
read
unsigned integer
***
read
unsigned integer
read
unsigned integer
read
unsigned integer
read
unsigned integer
read
unsigned integer
read
unsigned integer
read
unsigned integer
read
unsigned integer
read
unsigned integer
read
unsigned integer
read
unsigned integer
read
unsigned integer
read
unsigned integer
read
unsigned integer
read
unsigned integer
read
unsigned integer
3BHS109762 E01
SYN 5201/SYN 5202
Scaling
--
--
--
0.1 % of Un
0.1 DEG
0.01 %
0.1 % of Un
0.1 % of Un
0.01 Hz
0.01 Hz
0.01 %/s
Number of the selected
parameter set
One digit of the version
number per nibble (half
byte)
(e.g.: 5137d = 1411h =
V1.4.1.1)
none (0 to 65535)
none (0 to 65535)
none (0 to 65535)
none (0 to 65535)
none (0 to 65535)
none (0 to 65535)
none (0 to 65535)
none
none
none
none
none
none
none
none
page
en
D