Parameter Set - ABB SYN 5201 Operating Instructions Manual

Table of Contents

Advertisement

Operating Instructions
Events
Code
Description
032
Operating control interface
released
Status messages (displayed after expiry of the total paralleling time t tot)
Code
Description
 U outside of tolerance
051
band
052
s outside of tolerance band
 outside of tolerance band
053
054
 U within tolerance band
055
s within tolerance band
056
 within tolerance band
057
U1 or U2 above Umax
058
U1 or U2 below Umin
059
f1 or f2 outside of
fn  5 Hz
060
U1/U2<U0max and no
release for dead bus
061
No Stop command within
t tot
Faults
Code
Description
071
Synchronization fault
abb
ABB Switzerland Ltd
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
Remarks
Event is recorded only if the blocking signal is dropped
Remarks
If at least one voltage is
<U0max, but the release
for dead bus has not
been given
At least one paralleling
command from channel
1 has been given.
However, the expected
Stop signal has not
been generated
Remarks
Collective alarm
following expiry of total
paralleling time t tot
Document No Art Part
3BHS109762 E01
SYN 5201/SYN 5202
Remedy
If these messages are not desired,
they can be blocked by setting the
total paralleling time t tot to 0.
Otherwise, the following should be
checked, depending on the
combination of events:
Are both measuring voltages
continually present throughout
the entire synchronizing
process (observe LED)?
Was the calibration of the
measuring voltages carried out
correctly (see section 4.2.1)?
Are the set limit values correct?
Is the correct parameter set
active?
Are the voltage and frequency
matchers functioning correctly?
Automatic Stop signal is not
functioning
Command circuit is broken
SYN 5202: commands of ch 1
and ch 2 missed each other:
measuring voltage incorrectly
connected; see order of events
in the event list; refer also to
section 4.2.1 "  Offset"
Remedy
Check limit values for the
parameters
SYN 5202: Check synchro-
check parameters (ch 2) and
whether they match ch 1 (see
also section 4.2.9)
SYN 5202: Loss or error of
phase in one of both channels.
Read out other events which
may have been displayed at
the same time. Try to identify
the fault on the basis of the
combination