Addressing Lon-Bus
29 words, each with 16 bits, are transmitted. The addressing is as follows:
Add-
Content
ress
1
Digital inputs
2
Digital outputs
3
Digital outputs
4
Actual value U
5
Actual value 
6
Actual value s
7
Actual value U1
8
Actual value U2
9
Actual value f1
10
Actual value f2
11
Actual value ds/dt
12
Back-indication
of
parameter set
13
Software version
14
Command counter reading par-set 1 Analog val.
15
Command counter reading par-set 2 Analog val.
16
Command counter reading par-set 3 Analog val.
17
Command counter reading par-set 4 Analog val.
18
Command counter reading par-set 5 Analog val.
19
Command counter reading par-set 6 Analog val.
20
Command counter reading par-set 7 Analog val.
21
Current event (event code)
22
Year of the current event
23
Month of the current event
24
Day of the current event
25
Hour of the current event
26
Minute of the current event
27
Second of the current event
28
Hundredth of a second of the current
event
29
Digital inputs
*
read = read data from SYNCHROTACT 5
**
signed integer = whole numbers
***
unsigned integer = positive whole numbers
abb
ABB Switzerland Ltd
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
Word type
Direction
of trans-
mission
Bit-coded
read*
Bit-coded
read
Bit-coded
read
Analog val.
read
Analog val.
read
Analog val.
read
Analog val.
read
Analog val.
read
Analog val.
read
Analog val.
read
Analog val.
read
selected
Analog val.
read
Analog val.
read
read
read
read
read
read
read
read
Analog val.
read
Analog val.
read
Analog val.
read
Analog val.
read
Analog val.
read
Analog val.
read
Analog val.
read
Analog val.
read
Bit-coded
write
Document No Art Part
Format
Scaling
--
--
--
--
--
--
signed integer**
0.1 % of Un
signed integer
0.1 DEG
signed integer
0.01 %
signed integer
0.1 % of Un
signed integer
0.1 % of Un
signed integer
0.01 Hz
signed integer
0.01 Hz
signed integer
0.01 %/s
unsigned integer *** Number of the
selected parameter set
unsigned integer
One digit of the version
number per nibble (half
byte)
(e.g.: 5137d = 1411h =
V1.4.1.1)
unsigned integer
none (0 to 65535)
unsigned integer
none (0 to 65535)
unsigned integer
none (0 to 65535)
unsigned integer
none (0 to 65535)
unsigned integer
none (0 to 65535)
unsigned integer
none (0 to 65535)
unsigned integer
none (0 to 65535)
unsigned integer
none
unsigned integer
none
unsigned integer
none
unsigned integer
none
unsigned integer
none
unsigned integer
none
unsigned integer
none
unsigned integer
none
--
--
3BHS109762 E01
SYN 5201/SYN 5202
Signal name
NV_Syn5_inputs_out
NV_Syn5_output1
NV_Syn5_output2
NV_Syn5_delta_U
NV_Syn5_alpha
NV_Syn5_slip
NV_Syn5_U1
NV_Syn5_U2
NV_Syn5_f1
NV_Syn5_f2
NV_Syn5_ds_dt
NV_Syn5_Parameterset
NV_Syn5_SW_version
NV_Syn5_close1
NV_Syn5_close2
NV_Syn5_close3
NV_Syn5_close4
NV_Syn5_close5
NV_Syn5_close6
NV_Syn5_close7
NV_Syn5_event_code
NV_Syn5_event_year
NV_Syn5_event_month
NV_Syn5_event_day
NV_Syn5_event_hour
NV_Syn5_event_minute
NV_Syn5_event_second
NV_Syn5_one_hundredth
NV_Syn5_inputs
Language
Revision
page
en
D
56