Operating Instructions
d) Paralleling of asynchronous lines:
If two lines do not form a ring connection, the slip limits are restricted by the current
limit permitted after paralleling. If the flow of power in a particular direction is to be
avoided, the corresponding slip limit must be set to zero.
Angle limit, negative -  max and positive +  max
The permissible angle limit is based on different criteria, depending on the application:
a) paralleling of asynchronous sources.
b) paralleling of synchronous sources.
a) Paralleling of asynchronous sources:
The maximum permissible angle limit ±  max should generally be set symmetrically and
to 10 DEG.
If 3,6
fn
smax
*
*
Setting values above 15 DEG are not usual. If the calculation produces such a result, it
should be checked whether the maximum slip can be reduced.
b) Paralleling of synchronous sources:
The coupling reactance x
through these cause a phase shift between the two voltages U1 and U2.
abb
ABB Switzerland Ltd
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
t on+3 > 10 DEG, the value should be rounded up to whole degrees.
*
in ring mains lines and the balancing current I
K
Document No Art Part
3BHS109762 E01
SYN 5201/SYN 5202
flowing
K
Language
Revision
page
en
D
39