3Bhs109762 E01 - ABB SYN 5201 Operating Instructions Manual

Table of Contents

Advertisement

Operating Instructions
4.3.2
Configuring Modbus RTU
The configuration of the Modbus RTU is carried out using 14 DIP switches. The three
LEDs on the left next to the DIP switches are used for the status display.
The device has to be restarted each time the configuration is changed (switch auxiliary
Note
voltage off and on again).
OFF
ON
SWITCH
LEDS
If the SYNCHROTACT 5 device is configured in RS485 mode and is the last component
Note
on the bus, the blue switch (SWITCH) to the left of the LED's has to be set to ON in
order to prevent reflections on the bus line.
Function
Electrical mode
Selection of slave address
Selection of Baudrate
Selection of parity mode
Example:
Switch
DIP0
DIP1
OFF
0
0
SWITCH
Electrical mode
Slave address:
Baud rate:
Parity:
abb
ABB Switzerland Ltd
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
DIP0
DIP1
DIP2
DIP3
DIP4
DIP no.
DIP 0
DIP 1 – DIP 8
DIP 9 / 10 / 11
DIP 12 / 13
DIP2
DIP3
DIP4
DIP5
0
0
0
0
OFF
RS485
1
9600
None
Document No Art Part
1
0
DIP5
DIP6
DIP7
DIP8
DIP value
0
1
MSB - LSB
000
001
010
011
100
101
110
111
00
01
10
11
DIP6
DIP7
DIP8
DIP9
0
0
1
0

3BHS109762 E01

SYN 5201/SYN 5202
DIP9
DIP10 DIP11
DIP12
DIP13
Configuration
RS485
RS232
Valid range
1-247
1200
2400
4800
9600
19200
(factory setting)
38400
50000
Not supported
None
Odd
Even
Not used
DIP10
DIP11
DIP12
1
1
0
Language
Revision
page
en
D
1
0
DIP13
0
52

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Synchrotact 5Syn 5202

Table of Contents