Digital Input - ABB SYN 5201 Operating Instructions Manual

Table of Contents

Advertisement

Operating Instructions
4.3
Addressing and configuration of the operating interface
4.3.1
Addressing Modbus RTU
28 words, each with 16 bits, are transmitted. The addressing is as follows:
Add-
Content
ress
1
Digital inputs
2
Digital outputs
3
Digital outputs
4
Actual value U
Actual value 
5
6
Actual value s
7
Actual value U1
8
Actual value U2
9
Actual value f1
10
Actual value f2
11
Actual value ds/dt
12
Back-indication of selected parame-
ter set
13
Software version
14
Command counter reading parameter set 1
15
Command counter reading parameter set 2
Command counter reading parameter set 3
16
Command counter reading parameter set 4
17
18
Command counter reading parameter set 5
19
Command counter reading parameter set 6
Command counter reading parameter set 7
20
21
Current event (event code)
22
Year of the current event
23
Month of the current event
24
Day of the current event
25
Hour of the current event
26
Minute of the current event
27
Second of the current event
28
Hundredth of a second of the current
event
*
read = read data from the SYNCHROTACT 5
**
signed integer = whole numbers
***
unsigned integer = positive whole numbers
abb
ABB Switzerland Ltd
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
Word type
Direction
of
trans-
mission
read and
Bit-coded
write*
Bit-coded
read
Bit-coded
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Analog value
read
Document No Art Part
3BHS109762 E01
SYN 5201/SYN 5202
Format
Scaling
--
--
--
--
--
--
signed integer**
0.1 % of Un
signed integer
0.1 DEG
signed integer
0.01 %
signed integer
0.1 % of Un
signed integer
0.1 % of Un
signed integer
0.01 Hz
signed integer
0.01 Hz
signed integer
0.01 %/s
unsigned integer
Number of the selected
***
parameter set
unsigned integer
One digit of the version
number per nibble (half
byte)
(e.g.: 5137d = 1411h =
V1.4.1.1)
unsigned integer
none (0 to 65535)
unsigned integer
none (0 to 65535)
unsigned integer
none (0 to 65535)
unsigned integer
none (0 to 65535)
unsigned integer
none (0 to 65535)
unsigned integer
none (0 to 65535)
unsigned integer
none (0 to 65535)
unsigned integer
none
unsigned integer
none
unsigned integer
none
unsigned integer
none
unsigned integer
none
unsigned integer
none
unsigned integer
none
unsigned integer
none
Language
Revision
en
page
D
50