ABB SYN 5201 Operating Instructions Manual page 33

Table of Contents

Advertisement

Operating Instructions
Parameter sets 1 to 7
1. Actual value calibration "Calibrate act values"
No.
Parameter name
1.
Nominal voltage
2.
Nominal frequency
3.
Voltage tuning
4.
Angle tuning
2. Command generation "Paralleling cmd gen"
No.
Parameter name
1.
Test function
2.
Paralleling time
3.
Paralleling command duration
4.
Monitoring time
5.
Multiple commands
3. Paralleling conditions "Parallel conditions"
No.
Parameter name
1.
Slip limit, oversynchronous
2.
Slip limit, sub-synchronous
3.
Angle limit, negative
4.
Angle limit, positive
5.
Max. voltage difference, overexcited
6.
Max. voltage difference, underexcited
7.
Maximum voltage
8.
Minimum voltage
4. "Dead bus conditions"
No.
Parameter name
1.
Maximum zero voltage
2.
Release U1 = no-voltage
3.
Release U2 = no-voltage
4.
Release for U1 and U2 = no-voltage
5. "Voltage matcher"
No.
Parameter name
1.
Test function
2.
Voltage adjustment characteristic
3.
Pulse interval
4.
Minimum pulse duration
5.
Switchover to variable intervals
6.
Switchover to tap changer
6. "Frequency matcher"
No.
Parameter name
1.
Test function
2.
Frequency adjustment characteristic
3.
Pulse interval
4.
Minimum pulse duration
5.
Switchover to variable intervals
7. "General parameters"
No.
Parameter name
1.
Blocking time after selection
2.
Total paralleling time
abb
ABB Switzerland Ltd
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
Symbol
Range/resolution
Un
50 to 130
2
fn
16
/
, 50, 60
3
UOffset
12.0
Offset
180
Symbol
Range/resolution
TEST ton
ON/OFF
t on
0 to 990/10
tp on
OFF, 10 to 990/10
t supervis
0 to 99
MULTIPLE CMD
ON/OFF
Symbol
Range/resolution
-smax
0.00 to 6.00
+smax
0.00 to 6.00
0 to 99
-max
0 to 99
+max
0 to 40
-Umax
0 to 40
+Umax
Umax
105 to 130
Umin
50 to 95
Symbol
Range/resolution
U0max
0 to 49
U1not
ON/OFF
U2not
ON/OFF
1*2not
ON/OFF
Symbol
Range/resolution
TEST U-Match
ON/OFF
dU/dt
0.00 to 5.00
ts U
1 to 20
tp Umin
0.05 to 2.00
INVERSE U
ON/OFF
TAP CHANGER
ON/OFF
Symbol
Range/resolution
TEST f-Match
ON/OFF
df/dt
0.00 to 5.00
ts f
1 to 120
tp fmin
0.05 to 2.00
INVERSE f
ON/OFF
Symbol
Range/resolution
t block
1 to 10
t tot
OFF, 0.5 to 15/
Steps: 0.5
Document No Art Part
3BHS109762 E01
SYN 5201/SYN 5202
Unit
Default setting of all
parameter sets
VAC
110
Hz
50
%
0
DEG
0
Unit
Default setting of parameter
sets
1 to 6
7
-
OFF
OFF
ms
100
100
ms
990
OFF
s
10
10
-
OFF
OFF
Unit
Default setting of parameter
sets
1 to 6
7
%
0.4
0.2
%
0.4
0.2
DEG
10
10
DEG
10
10
%
3
3
%
3
3
%
120
120
%
80
80
Unit
Default setting of all
parameter sets
%
5
-
OFF
-
OFF
-
OFF
Unit
Default setting of parameter
sets
1 to 6
7
-
OFF
OFF
%/s
0.30
0.00
s
2
2
s
0.05
0.05
-
OFF
OFF
-
OFF
OFF
Unit
Default setting of parameter
sets
1 to 6
7
-
OFF
OFF
%/s
0.20
0.00
s
20
20
s
0.05
0.05
-
OFF
OFF
Unit
Default setting of all
parameter sets
s
2
min
5
Language
Revision
en
D
page
33