Operating Instructions
4.3.9
Configuration IEC 61850
The IEC 61850–Interface has two IP-addresses, the Service IP-address for the
configuration and the operating IP-address for the actual IEC 61850-Application.
Service PC
SynView
Synchronizing parameters, actual
values, event recorder, transient
recorder
SYN61850Config-Tool
Stack configuration SCD => CCF
IP address handling
PEC80 FW handling
IEC 61850 network
The Service IP-address is used for the configuration of the IEC 61850-Application, resp.
downloading of the SCD-file.
The service IP-address can be read out by means of the scan function of the
SYN61850Config-Tool (see chapter 7.4.3).
If necessary, the address can be adapted by means of the SYN61850Config-Tool.
The Factory Default Service IP-address is configured as follows:
IP-address:
Subnet Mask
Note
Each change requires a restart (Power up)
The Service IP-address must not be re-used in the connected subnet. If there are two or
Caution
more SYNCHROTACT 5 devices in the same subnet, the IP-addresses must be
different.
The operating IP-address for IEC 61850 is application-specific and is defined in the
SCD-File.
abb
ABB Switzerland Ltd
Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 3BHS109762E01 D.doc; Print: 12/6/2011 5:48:00 PM; Save: 12/1/2011 2:37:00 PM; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q
SYNCHROTACT 5
Synchronizing process
SynView
IP-address
IEC 61850 Communication
IEC 61850
Service IP-address
Operating IP-address (IEC 61850)
defined by the SCD file
10.10.10.11
255.255.255.0
Document No Art Part
3BHS109762 E01

SYN 5201/SYN 5202

S10001
Language
Revision
page
en
D
64