Connecting Output Contacts
(Optional)
(contd.)
Output Contact as
Labeled on Power
Labeled on Power
Board
Warning Contact
(System Warning)
Fault Contact
(System Fault)
Ready Contact
(System Ready)
NOTE A: The output contacts are not polarity sensitive. It does not matter which wire is inserted into a position.
Connecting External Devices to
the Pattern Control
A3EN-04-[3V-A-AAXP]-12
7. Connect the output wires to the plug for terminal block TB2 from the
ship-with kit. Refer to Table A 1-3.
Table A 1-3 Output Contact Connections
Behavior of Contact
Unit Power Off
Open
(no warning)
Open
Open
(unit not ready)
8. Connect the plug to TB2. See Figure A 1-13 for the location of TB2.
9. Go to the next procedure, Connecting External Devices to the Pattern
Control.
This procedure describes how to connect the following devices that
operate pattern control features:
a trigger device, which controls the operation of automatic gun
S
solenoid valves or the gun driver used with the pattern control feature
an optional enable/disable device, which sends a signal from a
S
remote location to enable or disable the pattern controller
the solenoid valves or gun driver that is used to activate the guns on
S
outputs 1 and 2
41-3000V
Issued 5/00
Unit Power On
Closed
Open
(warning exists)
Closed
Open
(no fault)
(fault exists)
Open
Closed
(unit ready)
TB2 Positions
TB2 Positions
(see Note A)
1, 2
3, 4
5, 6
E 2000 Nordson Corporation
All rights reserved