How To Add A New I/O Module; How To Remove Or Decommission An I/O Module - Honeywell Touchpoint Plus Wireless Technical Handbook

Hide thumbs Also See for Touchpoint Plus Wireless:
Table of Contents

Advertisement

3020M5001_Iss 1_07/18
Background color: Installed

8.4 How to add a new I/O Module

The Touchpoint Plus system can easily be expanded by adding new I/O modules.
Note: Engineer or higher level access is required
Note: A module which has previously been configured in one system cannot be added to another system,
unless it was correctly removed from the original system's configuration.
1) Switch off the Touchpoint Plus (Select Menu>Maintenance> Power off )
2) Isolate power supplies
3) Fit the new module of the required type to an empty slot, ensuring that that the module is the correct way
up and with the label towards you
4) Electrically connect the new module
5) Switch on the Touchpoint Plus
6) Login as an administrator
7) Select the Menu>Configuration>Module Control Panel
8) Select an empty block corresponding to the new module and touch 'Add'
9) Commission each channel in turn
Note: See Ch.7 Commissioning for detailed instructions for further information.

8.5 How to Remove or Decommission an I/O Module

If the relays are switching mains voltages, hazardous live terminals may be present within the Relay Output
Note: Engineer or higher level access is required.
1) Login as an administrator
2) Select Menu>Configuration>Module Control panel
3) Select the IO module block which is to be removed, and touch 'Remove'
4) Switch off the Touchpoint Plus (Menu>Maintenance>Power off )
Maintenance
Anti–Static Precautions
Antistatic Precautions are required to prevent severe damage to electronic components.
Module even if the Touchpoint Plus system is isolated.
Anti–Static Precautions
Antistatic Precautions are required to prevent severe damage to electronic components.
Warning
68
Touchpoint Plus Wireless
Technical Handbook