8.3 How to Replace a Faulty I/O Module

A faulty I/O module can be replaced with another of the same type, without needing to reprogram the
configuration. Touchpoint Plus will automatically copy over the configuration to the new module.
If the relays are switching mains voltages, hazardous live terminals may be present within the
Antistatic Precautions are required to prevent severe damage to electronic components.
Note: The new module must be the same type and the same number of inputs and outputs as the old module.
To replace a faulty module:
1) Switch off the Touchpoint Plus (Menu>Maintenance> Power off).
2) Isolate the power supplies and switch the battery to 'Off' (if there is a back-up battery installed).
3) Disconnect the faulty module.
4) Replace the module.
5) Reconnect the module.
6) Switch the battery to 'On' (if there is a back-up battery installed).
7) Switch on the TouchPoint Plus.
8) Login as an Administrator.
9) Select Menu>Configuration>Module Control Panel.
10) In the Board Control panel, select the empty blue block corresponding to the replaced module and touch
'Replace'.
Maintenance
Relay Output Module even if the Touchpoint Plus system is isolated.
Ensure that all current is isolated and dissipated before touching live terminals.
Anti–Static Precautions
Warning
Key to I/O Module colour
Gray: Mandatory modules that cannot be added removed
or replaced.
Yellow: A Module was added previously but cannot be
detected now (i.e. Module removed).
Light blue: Serial number or module type is not matched
(i.e. an I/O Module has been replaced).
Background colour: This module is installed.
67
Touchpoint Plus
Technical Handbook