Notices On Analog Specifications - Beckhoff EL34x3 Series Documentation

3-phase power measurement terminal
Table of Contents

Advertisement

Commissioning
Scaling factors EL34x3
Values EL3413-xxxx
Current (5 A)
Current (1 A)
Current (0.1 A)
[currently inactive on the
EL3413-0001]
Neutral conductor current (5 A)
Voltage
Active power
Apparent power
Reactive power
Energy
Power factor λ
Frequency
Angle α
Power factor cos φ
RMS value of harmonic
(Current 1 A)
RMS value of harmonic
(Current 5 A)
Ratio of harmonic to fundamental
RMS value of harmonic
Voltage
Table 1: Scaling factors for the calculation of the actual values from raw process data values
Technical data
All technical specifications apply to "3-phase 4-wire system with earthed neutral conductor", unless
explicitly stated otherwise.
Full scale value of the measuring range of the neutral conductor current
The full scale value of the measuring range of the neutral conductor current always corresponds to
the maximum current of the terminal (EL3413 = 5 A and EL3433 = 10 A) and cannot be switched.
5.6

Notices on analog specifications

Beckhoff I/O devices (terminals, boxes, modules) with analog inputs are characterized by a number of
technical characteristic data; refer to the technical data in the respective documents.
Some explanations are given below for the correct interpretation of these characteristic data.
140
Values EL3433-xxxx
Current (10 A)
Current (2 A)
Current (0.2 A)
Neutral conductor current
(10 A)
Voltage
Active power
Apparent power
Reactive power
Energy
Power factor λ
Frequency
Angle α
Power factor cos φ
RMS value of harmonic
(Current 2 A)
RMS value of harmonic
(Current 10 A)
Ratio of harmonic to
fundamental
RMS value of harmonic
Voltage
Version: 4.4
Calculation
Raw values x 0.000001 A x current
transformer ratio
Raw values x 0.000001 A x current
transformer ratio
Raw values x 0.000001 A x current
transformer ratio
Raw values x 0.000001 A x current
transformer ratio
Raw values x 0.0001 V x voltage
transformer ratio
Raw values x 0.01 W x current
transformer ratio x voltage
transformer ratio
Raw values x 0.01 VA x current
transformer ratio x voltage
transformer ratio
Raw values x 0.01 VA x current
transformer ratio x voltage
transformer ratio
Raw values x 0.001 Wh x current
transformer ratio
Raw values x 0.001
Raw values x 0.1 Hz; 0.01 Hz; 0.001
Hz
Raw values x 0.01°
Raw values x 0.001
Raw values x 0.000001 A x current
transformer ratio
Raw values x 0.000001 A x current
transformer ratio
Raw values x 0.01 %
Raw values x 0.0001 V x voltage
transformer ratio
EL34x3

Advertisement

Table of Contents
loading

This manual is also suitable for:

El3413-0000El3413-0001El3413-0120El3433

Table of Contents