Deactivation Of Central Account Management From Pcm600 - ABB RELION 670 SERIES Manual

Cyber security deployment guideline
Hide thumbs Also See for RELION 670 SERIES:
Table of Contents

Advertisement

1MRK 511 399-UEN B
5.3.3
670 series 2.2 IEC
Cyber security deployment guideline
Deactivation of Central Account Management from
PCM600
When Central Account Management is switched off in the IED, the IED will go
back to be open. There will not be any IED users defined even if that was the case
when Central Account Management was activated.
Instead the built-in, factory default users will be reactivated.
1.
Right click on the Device in Account Management tool and select Edit as
shown in figure
52
IEC15000292 V1 EN-US
Figure 53:
Deactivation of Central Account Management
2.
Select Device CAM Mode as Disable as shown in fig
3.
Click on Save & Close button, to save and close manual configuration screen.
4.
Right click on the Device, and select Write to IED as shown in fig
IEC15000293 V1 EN-US
Figure 54:
Write configuration to IED
5.
PCM600 output window indicates the result of the write operation as shown in
fig
55
Central Account Management
GUID-19BDC85E-4175-4B53-909F-0051E5D98492 v1
53
Section 5
54
61