Connection according to UL

Fusing data

Fusing data

Branch Circuit Protection (BCP)

Short Circuit Current Ratings (SCCR) with Standard Fuses and Circuit Breaker
(Tested per UL61800-5-1, reference UL file E132659)
These devices are suitable for motor group installation when used with Standard Fuses and Circuit Breaker.
For single motor installation, if the fuse value indicated is higher than 400 % of the motor current (FLA), the
fuse value has to be calculated. If the value of the fuse is below two standard ratings, the nearest standard
ratings less than the calculated value shall apply.
Inverters
Rated
Mains
power
kW
230 V, 1/3-ph
0.37
230 V, 1/3-ph
0.55 0.75
230 V, 1/3-ph
0.75
230 V, 1/3-ph
1.5
230 V, 3-ph
2.2
230 V, 3-ph
4
230 V, 3-ph
5.5
480 V, 3-ph
0.55 0.75
480 V, 3-ph
0.75
480 V, 3-ph
2.2
480 V, 3-ph
4
480 V, 3-ph
7.5
480 V, 3-ph
11
480 V, 3-ph
15
480 V, 3-ph
22
480 V, 3-ph
30
480 V, 3-ph
45
480 V, 3-ph
55
480 V, 3-ph
75
480 V, 3-ph
90
480 V, 3-ph
110
134
Standard Fuses (UL248)
SCCR
Max. rated current
HP
kA
A
0.5
65
35
65
35
1
65
35
2
65
35
3
65
35
5
65
60
7.5
65
60
65
35
1
65
35
3
65
35
5
65
35
10
65
60
15
65
60
20
65
60
30
65
70
40
22
125
60
22
125
75
22
200
100
22
200
125
22
300
150
22
300
Class
SCCR
Max. rated current Min. cabinet dimensions
kA
CC, CF, J, T
65
CC, CF, J, T
65
CC, CF, J, T
65
CC, CF, J, T
65
CC, CF, J, T
65
CC, CF, J, T
65
CC, CF, J, T
65
CC, CF, J, T
65
CC, CF, J, T
65
CC, CF, J, T
65
CC, CF, J, T
65
CC, CF, J, T
65
CC, CF, J, T
65
CC, CF, J, T
65
CC, CF, J, T
65
CC, CF, J, T
35
CC, CF, J, T
35
CC, CF, J, T
35
CC, CF, J, T
35
CC, CF, J, T
10
CC, CF, J, T
10
Circuit Breaker (UL489)
A
25
0.042
25
0.042
25
0.042
25
0.042
25
0.042
60
0.042
60
0.042
25
0.042
25
0.042
25
0.042
25
0.042
60
0.042
60
0.042
60
0.042
70
0.17
125
0.57
125
0.57
200
0.57
200
0.57
300
0.57
300
0.57
ft³
1.48
1.48
1.48
1.48
1.48
1.48
1.48
1.48
1.48
1.48
1.48
1.48
1.48
1.48
6
20
20
20
20
20
20