Validation On Demand - ABB Relion 630 Series Engineering Manual

Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

1MRS756800 F
5.1.7.2
630 series
Engineering Manual

Validation on demand

The validity of an application configuration can be checked by clicking Validate
Configuration in the toolbar. The Application Configuration tool checks the
application configuration for formal correctness. The found problems are divided into
warnings and errors.
Warnings, marked with a yellow warning icon
Example: a variable connected to an output signal that is not connected
Example: if an output from a higher execution order function is connected
to inputs of lower execution order function
Errors, marked with a red circle with a cross
Example: unconnected hardware output
Warnings do not prevent writing to the protection relay. However, errors must be
corrected before writing the application configuration to the protection relay. The
application configuration can be saved and the Application Configuration tool can be
closed with open errors, but the application configuration cannot be written to the
protection relay.
These problems are listed in the Output view under the Application Configuration
tab. Double-clicking the error or warning row navigates to the MainApplication/
Page/Area, where the problem was identified.
IEC09000614 V2 EN
Figure 41:
ACT: Validation on demand
Protection and control engineering
IEC09000614_2_en.vsd
Section 5