Using 630 Ieds In Com600 Project - ABB Relion 630 Series Engineering Manual

Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

1MRS756800 F
4.8
630 series
Engineering Manual
1.
Select an IED in the plant structure.
2.
Right-click and select the set technical key. A dialog window opens to inform
about the technical key concept.
3.
Click OK. The technical key is read from the IED and the Technical Key Editor
window opens.
4.
Select the way the technical key is defined.
Use the existing technical key in the IED.
Use the existing technical key defined for the IED object in PCM600.
Set a user-defined technical key, which changes the technical key for both
the physical IED and IED object in PCM600.
5.
Click OK to confirm the selection.
It is not possible to set a user-defined name or select the technical
key in IED if the value is the same as already given to another
IED object in the PCM600 project. A dialog window opens if
this is the case.

Using 630 IEDs in COM600 project

The 630 Connectivity Package does not have support for SAB600. This means that the
630 series IED needs to be imported as a generic 61850 device. It is also possible to
import a full PCM600 project including several 630 IEDs to SAB600. In this case
PCM600 project information is imported to SAB600 using a SCD file.
Procedure
1.
First create PCM600 project including several 630 IEDs.
IEC09000686 V1 EN
Figure 27:
Create PCM600 project including several 630 devices
2.
Export the SCD file from PCM600 and import it to SAB600.
Section 4
Setting up a project
IEC09000686-1-en.vsd
49

Advertisement

Table of Contents
loading

Table of Contents