Section 5
Protection and control engineering
5.1.7.3
5.2
64

Validation when writing to the protection relay

When writing the application configuration to the protection relay, an automatic
validation is performed. The validation is the same as the manually demanded
validation. Errors abort the writing.

Parameter Setting tool

Configuration and setting parameters can be changed either from LHMI or from the
Parameter Setting tool in PCM600.
Some parameters are only visible in Parameter Setting and some only
on LHMI.
A common write from PCM600 to the IED, where parameters are
changed in Parameter Setting, overwrites any parameter changes
made locally from the LHMI.
To export parameters from Parameter Setting, both XRIO and CSV
formats are supported.
Do not make Parameter Setting read/write operation to IED when
disturbance recorder is storing data since that causes PCM600 to
report that the IED is offline or having communication problems.
All variables listed and shown in the parameter list can be sorted into two groups.
Configuration parameters
Setting parameters
Configuration parameter
A configuration parameter specifies an operation mode of an application function or
of the IED. These are basic configurations, which are normally configured only once
and then settled. The IED configures itself at start-up according to the given
configuration parameter values.
Setting parameter
A setting parameter (short form only "setting") is a parameter that can be changed in
the IED at runtime.
1MRS756800 F
630 series
Engineering Manual