Section 5
Protection and control engineering
68
•
Operation of primary apparatuses
•
Overriding of synchrocheck
•
Select-Execute principle to give high reliability
•
Selection and reservation function to prevent simultaneous operation
•
Selection and supervision of operator place
•
Command supervision
•
Block/unblock of operation
•
Block/unblock of updating of position indications
•
Substitution of position indications
•
Overriding of interlocking functions
•
Operation counter
The apparatus control is realized by means of a number of function blocks designated:
•
LocalRemote switch (LOCREM)
•
Bay control (QCCBAY)
•
Switch controller (GNRLCSWI)
•
Circuit breaker (DAXCBR)
•
Circuit switch (DAXSWI)
The three latter functions are logical nodes according to IEC 61850. The signal flow
between these function blocks is shown in
these functions can be found in technical manual. Logical node for interlocking
(SCILO) in
Figure 45
is the logical node for interlocking. Control operation can be
performed from the LHMI.
Figure
45. The detail description for all
1MRS756800 F
630 series
Engineering Manual