Section 7
IEC 61850 communication engineering
7.7.7
122
Data set entries for vertical reporting are selected using the data object
level, and entries for GOOSE using the data attribute or data object
level.

Creating report control blocks with IET600

Configuration properties, such as the attached data set and the buffering and triggering
options of the RCBs are are defined in the RCB editor. A predefined RCB
configuration of a preconfigured IED is a proposed default configuration which can
be adapted according to the requirements.
1.
Click an IED node in the IEDs navigation pane.
2.
Click the RCB Data tab in the editor pane.
3.
Right-click the area containing RCB names and select Insert new row.
4.
Define the LN where the RCB is to be placed (preselected LD0/LLN0 is
recommended) and the name for the new RCB.
Use the field chooser to show or hide the properties. For example, SeqNum,
Entry ID and Reason Code options, set by default in the IED, are hidden by
default.
GUID-B40C1703-845C-492A-8350-3B0559C730C9 V2 EN
Figure 94:
RCB editor
Conf.Rev cannot be manually edited. IET600 updates it automatically
to the next multiple of 100 when the configuration changes.
Deleting an RCB does not totally remove it from IET600. Instead, its
status is set to "Deleted" and it is not exported to SCL files. Removing
a data set automatically puts the related RCB to the "Deleted" state.
An RCB cannot be renamed. To rename an RCB, delete it and create
a new RCB with a new name.
1MRS756800 F
630 series
Engineering Manual