Changed Functions - ABB Relion 630 Series Engineering Manual

Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

Section 10
Configuration migration
10.2.7
142

Changed functions

Table 4:
Functions changed in the configuration after the migration from 630 series Ver. 1.0 to
630 series Ver. 1.1
Function
Implication
1)
SCILO
All instances are removed from ACT.
1)
SPGGIO
All instances are removed from ACT.
1)
DPGGIO
All instances are removed from ACT.
The function is removed from the Application Configuration tool. The signal is now
1)
PSM_BATSUP
available in the PSM module analog inputs.
The function is removed from the Application Configuration tool. The signal is now
1)
PSM_TCS
available in the PSM module analog inputs.
The function is removed from the Application Configuration tool. The signal is now
1)
A3RADR
available in the PSM module analog inputs.
DEFLPDEF
New setting Base value Sel phase added.
DEFHPDEF
New setting Base value Sel phase added.
INTRPTEF
Setting Ground start value renamed to Voltage start value.
SCEFRFLO
Amount of recorded data banks increased.
DARREC
CB closed Pos status setting default value changed to 0.
DSTPDIS
Setting Voltage Mem time added.
Minimium values for Operate time delay, Dead line time and Cur voltage Det time
CVRSOF
and step resolution for all time settings.
MNSPTOC
DO type corrected.
Removal of setting Base value Sel Res. Now internal minimum current levels are
LREFPNDF
also based on phase base values.
Harmonized default value for setting Scheme type with the default of the same
RESCPSCH
setting in DSOCPSCH.
GNRLCSWI
Changed default for input SYNC_OK to TRUE.
SSCBR
DOs PosOpn and PosCls removed from the default data set.
The time quality for mandatory data SeqA.c3 (showing always zero amplitude) is
CSMSQI
corrected.
The time quality for mandatory data SeqV.c3 (showing always zero amplitude) is
VSMSQI
corrected.
1) The function must always be reassigned if it has been used in the earlier configuration.
Table 5:
Functions changed in the configuration after the migration from 630 series Ver. 1.1 to
630 series Ver. 1.2
Function
Implication
1)
EPDMMTR
Function is removed from ACT.
COM
Debounce time lower limit changed for binary input.
BIO
Debounce time lower limit changed for binary input.
MAPGAPC
Under-operation mode corrected.
MNSPTOC
IEC and ANSI symbols updated.
Table continues on next page
1MRS756800 F
630 series
Engineering Manual